Cover2c.jpg
Water Facts
Introduction - Home Page
Drought - Assuring Our Water Supply
Preserve & Conserve:Water Conservation
Recharging Groundwater and Water Reuse
City of Peoria Utilities Department
Treated Tested Safe
Water Quality Center - Rose Valley
Water Quality Data
About This Report
Cover Page
 
 
Water Quality Data
Water Quality Data
Page 10: Arsenic, Lead & Copper, Radiological
Page 11: Aesthetics, Turbidity
Page 12: Inorganics
Page 13: Organics, Disinfection Byproducts, Other Analyses
Page 14: Definitions & Abbreviations, 2002 & 2003 Violations

Aesthetics 

Aesthetic contaminants occur naturally and are monitored because of their effect on taste and clarity. 

 

 

Groundwater Concentrations

Greenway Surface Water Concentration

Pyramid Peak Surface Water Maximum Concentration

EPA Limit 

EPA Limit 

 

Analyte

Units

Range

Average

Range

Average

Range

Average

MCL

MCLG

Sample Date

Alkalinity

mg/l

96-186

133

124-169

148

NA

NA

NA

NA

2002

Calcium

mg/L

6-52

31

NA

NA

NA

NA

NA

NA

2002

Chloride

mg/l

NA

NA

NA

NA

78

78

NA

250

2000

Geosmin

ug/L

NA

NA

0

0

0.002-0.005

0.003

2001/02

Hardness

Gr/gal

1.3-13.7

10.6

236*

236*

NA

NA

NA

NA

2002

Iron

mg/L

0-3.2

0.3

NA

NA

0.059

0.059

NA

0.3

2001/02

Magnesium

mg/L

2-27

14

27*

27*

214

214

NA

NA

2001/02

Manganese

mg/L

0.002-0.1

0.016

NA

NA

NA

NA

NA

0.05

2002

Methylisoborneol (MIB)

ug/L

NA

NA

0

0

0.002-0.027

0.008

2002

pH

7.5 - 8.8

8.0

8.0

8.0

7.7

7.7

NA

NA

2001/02

Total Dissolved Solids

mg/l

220-796

329.0

664*

664*

574-652

613

NA

NA

2002

Sulfate

mg/l

24 - 210

31

98*

98*

231

231

NA

250

2002

Sodium

mg/l

77*

77*

193*

193*

NA

NA

NA

NA

2002

* Only one sample required. 

Turbidity 

Turbidity is caused by soil run off and is a measure of the cloudiness of the water. It is a good indicator of the effectiveness of filtration systems. 

Surface Water Source

Units

Level Found

Range

MCL

MCLG

Sample Date

Peoria Greenway

NTU

0.107

NA

TT=1 NTU

0

2002

100%

NA

TT= % of samples <0.3 NTU

0

Glendale Pyramid Peak

NTU

0.18

NA

TT=1 NTU

0

2002

100%

NA

TT=%of samples <0.3 NTU

0

TT="Treatment technique" - a required process to reduce the level of a contaminant in drinking water 

NOTES: Turbidity has no health effects. However, turbidity can interfere with disinfection and provide a medium for microbial growth. Turbidity may indicate the presence of disease-causing organisms. These organisms include bacteria, viruses, and parasites that can cause symptoms such as nausea, cramps, diarrhea, and associated headaches.

Water Qulaity Data Page 2
e-mail: utilities@peoriaaz.gov

>>>NEXT

New Page 2

| Water Facts  | Introduction (Home)  | 
 
Drought-Assuring Our Water Supplies
Preserve and Conserve-Water Conservation  |
| Recharging Groundwater and Water Reuse | Treated-Tested-Safe  |
 
| Water Quality Center-Rose Valley  | Water Quality Data |
| About this Report | Cover Page | Utilities Department |
| peoriaaz.gov |

Download PDF of the entire 2003 Water Report (1.51MB)